Solar Battery Calculator
Estimate battery capacity in kWh and Ah for an AC load and autonomy target, with optional solar recharge sizing that includes ongoing daily demand.
Tell us more, and we'll get back to you.
Contact UsAbout Solar Battery Calculator
Practical context, assumptions, examples, and next steps for using the result well.Size battery energy, not inverter output power
This solar battery calculator estimates nominal stored energy needed to support a chosen AC electricity load for a specified autonomy period. It accounts for an allowed depth of discharge and an aggregate inverter-plus-discharge efficiency. The main outputs are nameplate capacity in kilowatt-hours, an equivalent amp-hour capacity at a selected nominal voltage, and the energy delivered to AC loads after the modeled reductions.
Battery energy and output power answer different questions. Kilowatt-hours indicate how much energy can be supplied over time. Kilowatts indicate how quickly it can be supplied. A battery with ample stored energy may still be unable to run a large appliance because its inverter, battery management system, or discharge-current limit cannot support the required instantaneous power. Motor starting surges can exceed normal operating demand and need separate assessment.
The optional solar recharge mode adds a daily energy-balance calculation. It estimates an array that covers ongoing daily demand while replacing the usable reserve consumed during the autonomy period. This is useful for comparing backup recovery or preliminary off-grid scenarios, but it does not establish reliable off-grid operation. There is no hourly dispatch model, equipment compatibility check, or live weather data. All efficiency, sunlight, and operating-window values are assumptions you can edit rather than recommendations for a specific battery.
Define AC loads and the autonomy period
Enter the daily energy consumed by the AC loads that the battery must support. For essential-load backup, that may be a refrigerator, selected lights, communications equipment, and a few other circuits rather than the entire home. Use measured consumption where possible. A device averaging 50 W over a full day uses 1.2 kWh. Its brief peak power may matter for inverter sizing, but average energy is what belongs in this input.
Autonomy is the number of equivalent load days supported without replenishment. A 5 kWh daily load with two days of autonomy requires 10 kWh delivered to those AC loads. The calculator treats that as a reserve that starts fully available and is consumed down to the chosen discharge boundary. It does not assume solar production during the autonomy interval. Fractional days are accepted, so half a day represents half of the entered daily energy.
Think carefully about behavior during an outage. Electric cooking, space heating, water heating, and vehicle charging may dominate ordinary consumption but be reduced or excluded during backup operation. Conversely, a medically necessary or continuously operating load should not disappear from the estimate just because it is small. Document the intended load list and use the same definition when comparing equipment. The calculator does not automatically add standby consumption, unexpected use, or a critical-load safety reserve.
Battery capacity formulas and a worked example
Let daily AC energy be E, autonomy be A, allowed depth of discharge be d as a fraction, and aggregate discharge efficiency be ηd. Required delivered energy is E × A. Nameplate battery energy is E × A ÷ (d × ηd). Dividing by depth preserves the fraction of nameplate capacity that you do not intend to use. Dividing by discharge efficiency allows for the energy lost before the selected AC loads receive it.
For example, a 5 kWh daily AC load over two days requires 10 kWh delivered. With 80% depth of discharge and 90% inverter-plus-discharge efficiency, nameplate capacity is 10 ÷ 0.8 ÷ 0.9 = approximately 13.889 kWh. The permitted withdrawal is about 11.111 kWh on the stored-energy side, and the modeled output path delivers 90% of that, or 10 kWh, to the AC loads.
The displayed capacity is a continuous arithmetic minimum, not a rounded equipment selection. Real batteries come in particular module sizes and have specific usable-capacity definitions. Choose a compatible product configuration with adequate capacity and any required additional margins, rather than assuming a product can be purchased in exactly the calculated amount. The form rejects zero depth, zero efficiency, nonfinite values, and extreme combinations that cannot produce finite, meaningful results. It never turns an invalid sizing case into a zero-capacity recommendation.
Depth of discharge, losses, and battery chemistry
Depth of discharge describes the fraction of nameplate energy that is allowed to be withdrawn. An 80% setting means the model uses 0.8 of nominal energy and leaves the remainder outside the planned discharge window. It is not the same as an 80% loss. Increasing allowed depth reduces the calculated nameplate capacity, but whether that operating window is appropriate depends on the product, chemistry, temperature, warranty, and intended cycle life.
The discharge efficiency combines losses on the path from stored energy to the chosen AC load boundary. Use a documented or justified aggregate that fits your equipment and avoids double counting. If a specification provides round-trip efficiency, do not automatically enter it as both charging and discharging efficiency. Round-trip efficiency combines multiple stages; applying the same combined figure to each stage would exaggerate losses. Inverter standby consumption may also need a separate energy allowance rather than a constant efficiency.
Lithium-based products and lead-acid products do not share one universal discharge limit or charging behavior. Lead-acid capacity can vary with discharge rate, while lithium systems depend on their management and protection limits. Low temperatures, high temperatures, aging, and operating power can change usable energy. The example defaults are not chemistry recommendations. If a manufacturer already quotes usable AC-delivered capacity, first reconcile that rating with these inputs so that depth and conversion reductions are not applied twice.
What the amp-hour result means
For an ideal nominal-energy conversion, watt-hours equal nominal voltage multiplied by amp-hours. The calculator therefore converts nameplate kWh to Ah by multiplying by one thousand and dividing by nominal bank voltage. The 13.889 kWh example at 48 V gives approximately 289.352 Ah. At 24 V, the same nominal energy corresponds to approximately 578.704 Ah. The energy requirement has not changed; only its nominal voltage-based expression has.
Nominal voltage is a reference label, not a statement that battery voltage remains constant throughout discharge. Actual voltage depends on chemistry, state of charge, temperature, and operating conditions. Manufacturer energy ratings can therefore be more useful than reconstructing energy from a rounded nominal voltage and an amp-hour label. Compare ratings on the same basis, including the stated test conditions and whether capacity is nominal, usable, DC-side, or AC-delivered.
The amp-hour output does not specify a wiring arrangement. It cannot tell you how many modules may safely be placed in series or parallel, which batteries are compatible, or what protection and cable sizes are required. Nor does a higher selected nominal voltage automatically make a particular product suitable. This calculator intentionally provides no connection instructions. Treat the voltage input as a way to interpret capacity, then rely on approved equipment documentation and qualified design for actual system architecture.
Solar recharge must cover ongoing daily demand
Reserve recovery adds demand beyond ordinary operation. If the household continues using energy while the battery is replenished, an array sized only to replace the depleted reserve will fall short. This model adds the daily AC load to the reserve's AC-equivalent energy divided by the requested recharge days. It then converts that combined daily target to a PV energy requirement using both charging and discharging efficiency.
Let recharge time be R and charging efficiency be ηc. Daily PV energy for ongoing demand is E ÷ ηd ÷ ηc. Daily PV energy for reserve recovery is (E × A) ÷ R ÷ ηd ÷ ηc. These quantities describe energy needed after PV-system losses but before the battery charging stage. Required DC array power is their sum divided by peak sun hours and by the PV retained fraction, defined as one minus PV loss divided by one hundred.
The model conservatively routes all daily demand through storage. Some real systems can supply daytime loads directly and avoid part of that storage path. Conversely, charge taper, scheduling, and controller limits can make recovery slower than an ideal daily balance suggests. The separate PV loss input should exclude battery charging and discharge losses already represented by their own efficiencies. Unlike a full installed solar design, this calculation uses one average daily sun assumption and does not simulate the sequence of cloudy and clear hours.
Worked example: restore the reserve while serving the load
Continue with a 5 kWh daily AC load, two autonomy days, 80% depth, and 90% discharge efficiency. Suppose the depleted usable reserve must be restored over two days, charging efficiency is 95%, peak sun hours are four per day, PV loss is 20%, and each panel is rated at 400 W. The normal daily demand remains 5 kWh. Restoring the 10 kWh delivered reserve over two days adds another 5 kWh per day on an AC-equivalent basis.
Each of those two daily components requires 5 ÷ 0.9 ÷ 0.95 = approximately 5.848 kWh of PV energy after PV losses. Their combined target is approximately 11.696 kWh per day. Dividing by four sun hours and by 0.8 gives a required array of approximately 3.655 kW DC. Dividing by 0.4 kW per panel and rounding upward produces ten panels, or 4 kW installed. Modeled daily PV output after PV losses is 4 × 4 × 0.8 = 12.8 kWh.
If the recharge period increases to four days, the ongoing-demand component stays unchanged while the reserve-recovery component halves. Reducing allowed depth of discharge instead increases required nameplate battery capacity, but does not increase the energy consumed by the same AC loads. That is why depth affects the battery size without independently multiplying recharge energy in this model. These distinctions help avoid oversizing through double counting or undersizing by forgetting continuing consumption.
Weather, reserve margins, and safe interpretation
A daily average cannot prove reliability during a sequence of poor solar days. An off-grid system needs analysis of seasonal resource, hourly load timing, starting state of charge, acceptable outage risk, and any alternative energy source. The recharge result assumes the entered sunshine repeats and that the equipment can accept the calculated energy within available hours. It does not model a charging power limit, a controller bottleneck, or taper near full charge.
No extra allowance for degradation, low-temperature capacity reduction, unplanned loads, or a protected emergency reserve is built into the nameplate result. Those allowances depend on the application and product. A designer may choose greater capacity, lower planned depth, or a different load-management policy. Make such changes explicit and avoid applying the same reserve twice. Numerical precision is not an assurance that battery performance will match the estimate throughout its service life.
Battery installations involve substantial stored energy and product-specific electrical and fire-safety requirements. Chemistry, ventilation requirements, placement, environmental limits, protection, and local regulations need qualified assessment. This page offers no wiring, charging-profile, or installation instructions. Separately verify inverter continuous output and surge capability, battery discharge limits, permitted charge rates, and system compatibility. Use the linked laboratory models and manufacturer information to develop a detailed assessment rather than relying on this energy estimate as a complete equipment design.
Frequently Asked Questions
How much battery capacity supports 5 kWh daily for two days?
The AC energy target is 10 kWh. At 80% allowed depth of discharge and 90% inverter-plus-discharge efficiency, required nameplate capacity is 10 divided by 0.8 divided by 0.9, or about 13.889 kWh. At a nominal 48 V this is approximately 289.352 Ah, before any aging, temperature, or additional reserve allowance.
What is the difference between nameplate and usable delivered energy?
Nameplate capacity is the nominal stored energy before applying the selected discharge window and output losses. Usable delivered energy is what the model makes available to the AC loads after both reductions. Do not apply depth of discharge twice if a manufacturer's advertised capacity is already a usable-energy rating.
Does the Ah result specify how batteries should be connected?
No. Amp-hours are calculated from nameplate energy and nominal bank voltage, so they are only an equivalent capacity figure. They do not specify series or parallel arrangements, protection, cable sizes, or compatible battery modules. Follow manufacturer requirements and qualified installation guidance rather than treating this result as wiring advice.
Why does solar recharge sizing include ongoing daily consumption?
An array must supply the normal load while also replacing energy used during the autonomy period. For a 5 kWh daily load and a depleted 10 kWh delivered reserve restored over two days, the daily AC-equivalent target is 5 plus 5, or 10 kWh. The calculator then accounts for charge, discharge, and PV losses before rounding the panel count upward.
Can the battery run a large motor if the kWh result is sufficient?
Not necessarily. Energy capacity determines duration, while inverter continuous output, starting surge, battery current limits, and control settings determine whether a load can operate at all. A large battery with an undersized inverter may still be unable to start a pump. This calculator does not size instantaneous power or surge capability.
Are the default depth of discharge and efficiencies safe for every chemistry?
No. Lithium-based and lead-acid batteries have different discharge limits, temperature behavior, cycle-life tradeoffs, and charge requirements. The defaults are arithmetic examples, not equipment recommendations. Use the allowed operating window and measured or documented efficiencies for the specific product and installation.
Does the recharge estimate guarantee reliable off-grid operation?
No. It assumes identical daily sun availability and distributes reserve recovery evenly over the selected days. It omits storm sequences, hourly load timing, charge taper, controller limits, and battery degradation. Reliable off-grid planning needs time-series resource and load analysis, appropriate reserves, and professional assessment.